VOLTAGE
Measurement Range 10-300 VAC(L-N), 10-500 VAC (L-L)
Measurement Range wite VT 10 - 200 kV
Voltage Accuracy 0.5% ± 1 1digit
Input Impedance 1.8 MΩ
Burden (Imput Load) <0.5 VA
CURRENT
Current Accuracy 0.5% ± 1 1digit
Nominal Current 1A/5A
Minimum Current 5 mA
Measurement Range 50mA - 5.5A
Measurement with CT 50mA-10000A
Burden (Input Load) <1VA
Overload Current 1.2 In
POWER/ENERGY
Active Power Accuracy 0.5% ± 1 1digit
Reactive Power Accuracy 1(s)% ± 1 1digit
Active Energy Accuracy Class 1
Reactive Energy Accuracy Class 2
Active Power Range 0-215 MW
Reactive Power Range 0-215 MVAr
Apparent Power Range 0-215 MVA
Active Power Indicating Range 9999999.9 kWhr
Reactive Power Indicating Range 9999999.9 kVArh
Supply
Operating Voltage 185-315 VAC ; 45 - 65 Hz
Network Type 3-phase/3-wire(Aron)
3-phase/3-wire(Delta)
Communication
Communication RS-485
Baud Rate 1200 - 115000 bps
Imput/Output
Digital Input Pulse Width 120/500 ms
Digital Input Operating Voltage 12 - 48 VAC/DC
Switching Current Max. 50 mA
Switching Voltage Max. 30 VDC
Pulse Width 20 - 500 ms (Adjustable)
Mechanical Parameters
Equipment Protection Double Insulation, Measurement Category lll
Ambient Operting Temperature -5 °C, +55°C
Degree of Protection IP40(front panet)
Panel Cut Out (mm.) 68x68 mm.
Dimensions 72x72 mm.


This website uses cookies (Learn more) and has a privacy policy (Learn more).